Preliminary and intermediate filter

 
Method of use:
 
For the pre filtration in ventilation systems and devices of all kinds up to fine dust filtration.
 
 
Measurements:
 
bullet
910 x 610 x 47 mm, Filter quality G3 (EU3) and G4 (EU4)
bullet
610 x 610 x 47 mm, Filter quality G3 (EU3) and G4 (EU4)
bullet
596 x 596 x 47 mm, Filter quality G3 (EU3) and G4 (EU4)
bullet
610 x 305 x 47 mm, Filter quality G3 (EU3) and G4 (EU4)
bullet
305 x 305 x 47 mm, Filter quality G3 (EU3) and G4 (EU4)
 
 
Model cellular filter:
 
 
Quality class G3 (EU3)
Quality class G4 (EU4)
Frame
cardboard frame, 47 mm wide
cardboard frame, 47 mm wide
Filter medium
Glass wool
Synthetic
Filtration efficiency (Am)
85 %
90 %
Nominal volume flow
5400 m³/h/m²
5400 m³/h/m²
Nominal blow speed by nominal volume
1,5 m/s
1,5 m/s
Starting pressure difference
30 Pa
42 Pa
Recommended final pressure difference
450 Pa
250 Pa
Temperature/humid air
00°C/100% RF
100°C/100% RF (relative humidity)
 
 